In the paper is presented experimental analysis and diagnostics of insulating system oil-paper for power transformers. In the first part of the paper is described base theory about measurement and diagnostics insulating part (oil and paper) of transformers. In the other two parts of the paper is presented experimental results of the diagnostic measurement for the transformer 22/0.4 kV at constant temperature. Specifically, in the second part is described measuring time method of insulating diagnostics - return voltage measurement (RVM). This method is used for analysis of condition of paper moisture of high-voltage equipment. In the third part is described measuring method of insulating frequency diagnostics - frequency domain spectroscopy (FDS). This method is used for analysis insulating condition of high-voltage equipment with insulating oil-paper. The both measuring methods are unique in terms of analysis of insulating system of oil power transformers. In comparison with other methods, the RVM and FDS methods it is possible comparison and evaluate the moisture state of the dielectric paper of the power transformer with high reliability and accurate. Their reliability in determining moisture in paper was shown by determining the same result (3.5%) on the same measured transformer.
REFERENCES(17)
1.
Brandt, M. Identification failure of 3 MVA furnace transformer. IDEMISEE 2016, Papradno, SR, 2016: 6-10.
Petras J, Kurimsky J, Balogh J, Cimbala R, Dzmura, J, Dolnik B, Kolcunova I. Thermally stimulated acoustic energy shift in transformer oil. Acta Acustica United with Acustica. 2016;102(1):16-22. https://doi.org/10.3813/AAA.91....
Glowacz A. Acoustic-Based Fault Diagnosis of Commutator Motor. Journal of Magnetism and Magnetic Materials. Electronics. 2018;7(11):299. https://doi.org/10.3390/electr....
Glowacz, A. Acoustic fault analysis of three commutator motors. Mechanical Systems And Signal Processing. 2019;133: 106226. https://doi.org/10.1016/j.ymss....
Shayegani AA, Hassan O, Borsi H, Gockenbach E, Mosheni H. PDC measurement evaluation on oil-pressboard samples. International Conference on Solid Dielectrics. 2004; 4: 50-62.
Leibfried T, Kachler AJ. insulation diagnostics on power transformers using the polarisation and depolarisation current (PDC) analysis. International Symposium on Electrical Insulation. 2002;10:170-173.
Koch M, Tenbohlen S, Krüger M, Kraetge A. A Comparative Test and Consequent Improvements on Dielectric Response Methods. Proceedings of the XVth International Symposium on High Voltage Engineering, ISH, Ljubljana, Slovenia, 2007.
Koch M. Reliable moisture determination in power transformers. PhD thesis, Institute of Energy Transmission and High Voltage Engineering, University of Stuttgart, Sierke Verlag Göttingen, Germany, 2008.
Šulka P, Sapietová A, Bárnik F. Vibrodiagnostics of rolling ball bearings connected with processing, result´s comparison and prediction of service life. Scientific Journal of Silesian University of Technology. Series Transport. 2020; 106: 183-196. https://doi.org/10.20858/sjsut....
Andrearczyk A, Bagiński P. Vibration analysis of a turbocharger with an additively manufactured compressor wheel. Scientific Journal of Silesian University of Technology. Series Transport. 2020; 107:05-17. https://doi.org/10.20858/sjsut....
We process personal data collected when visiting the website. The function of obtaining information about users and their behavior is carried out by voluntarily entered information in forms and saving cookies in end devices. Data, including cookies, are used to provide services, improve the user experience and to analyze the traffic in accordance with the Privacy policy. Data are also collected and processed by Google Analytics tool (more).
You can change cookies settings in your browser. Restricted use of cookies in the browser configuration may affect some functionalities of the website.